Monday, December 14, 2015

Fiber Patch Cable Management

Deploying more fiber optic cable is just the first step to meet the high-bandwidth requirements, strong management over the fiber optic cable is a basic requirement for a successful fiber optic network infrastructure. Fiber patch cable might be the weakest link in optical network infrastructures. To deliver and guarantee and optimal network performance, patch cable management is critical. In addition, well management of fiber patch cable can lower operation cost & time and increases the reliability and flexibility of network operation and maintenance. This post will offer the critical elements that should be noted during patch cable management, as well as tips for fiber patch cable management.
Elements That Affects Patch Cable Management
To get a flexible and well organized patch cable management, the factors that affect the performance of the fiber optic patch cable should be introduced first. Here are four key elements that should be considered during patch cable management.
Bend Radius
Unlike copper, fiber optic made of glass is much fragile and need more protection and attention during the operation and management. Thus, the fiber’s bend radius will impact its reliability and performance. If a fiber cable is bent excessively, the optical signal within the cable may refract and escape through the fiber cladding which will cause a loss of signal strength and is known as bend loss. What’s more, bending, especially during the installation and pulling of fiber optic patch cable might also cause micro cracks and damage the fiber permanently. Generally, there are two basic types of bends in fiber, which are microbends and macrobends as shown in the following picture. The macrobends are larger than microbends.
bend radius
What should be noted is that bend radius might not be seen during the initial installation of fiber patch cable. This is because the number of patch cables routed to the optical distribution ODF is usually small. However, when more patch cords are added on the top of installed patch cables in the future the problems will come across (shown in the following picture). A fiber patch cable that working fine for years might suddenly have an increased level of attenuation, as well as a potentially shorter service life.
effect of adding cable
Path of Patch Cable
Patch cable path is an aspect closely related to bend radius that can affect the performance and maintenance of the patch cable. The path of the patch cable should be clearly defined and easy to follow. Improper cable routing can cause increased congestion in the termination panel, increasing the possibility of bend radius violations and long-term failure. However, the well managed patch cable path ensures that bend radius requirements are maintained at all points and makes accessing individual patch cable easier, quicker and safer. What should be mentioned is that the well organized fiber patch cords can help to decrease operating costs and the time required to turn-up or restore service.
Accessibility of Patch Cable
The third aspect is accessibility of the installed patch cable. If the installed patch cable is easy to be accessed, the maintenance and operation would be quick without inducing a macrobend on an adjacent fiber, and it can also offer proper bend radius protection. Accessibility is critical during network reconfiguration operations and directly impacts operation costs and network reliability.
Physical Protection
Patch cables routed between pieces of equipment can largely affect network reliability. Without proper protection, they would be easy to be damaged by technicians and equipment accidentally. Thus, physical protection of the installed patch cords is very important.
Tips for Fiber Patch Cable Management
According to the mentioned aspects that can affect the performance and maintenance of the fiber optic patch cable, here offers several tips that can help to increase the performance of patch cords, as well as the reliability and flexibility of patch cable management.
Tip 1: Pay attention to the bend radius of the patch cable. Generally, for 1.6mm and 3.0mm cords the minimum un-loaded bend radius is 3.5 cm, and the minimum bend radius of MPO patch cable is ten times the cord diameter.
bend radius of fiber optic
Tip 2: Never pull or stress the patch cords (shown in the following figure). During the patching process, excessive force can stress fiber patch cables and connectors attached to them, thus reducing their performance. There might be something wrong if you need to use force in pulling a cord.
pulling fiber patch cable
Tip 3: Routing cords through cable pathways. If the existing cord is the right length, it may be possible to re-use it. If this is the case, remove the cord completely and re-run it in through the cable pathways. This is the only sure way to ensure there are no tangles, kinks or strains in the cord. For efficient routing, find the best path between the ports to be connected. Avoid routing cords through troughs and guides that are already congested.
Tip 4: Bundling and tying cords gives the panel a neat appearance but tight bundling increases the risk of pinching (shown in the following figure). Do not tighten cable ties beyond the point where individual cords can rotate freely.
bundling cable
Tip 5: Labeling is necessary. Labeling is the most important part of a System Administrator’s responsibilities. At any administration point in a cabling infrastructure, including patching panels, accurate labels are essential. These will identify pair modularity and tell technicians where the other end of the cable is terminated.
Tip 6: Inspect fiber cords for physical damage including stress marks from sharp bends on the sheath, or damage to connectors as shown in the following figure.
physical damage
Conclusion
A strong and successful patch cable management which can increase the reliability and flexibility and decrease the cost of network operation and maintenance should provide bend radius protection, reasonable patch cable path, easy accessibility of patch cable and physical protection. When the four mentioned aspects are satisfied, there is already half the success to strong patch cable management.

Monday, December 7, 2015

Causes of Mechanical Splice Termination Failures

FTTH (fiber to the home) has become increasingly popular in optical communication industry. Fiber optic termination, as one of the topics which have never been out of fashion in this field, has naturally become a focus of FTTH network deployment, especially the indoor termination. In FTTH network, mechanical splice connectors are usually used in FTTH indoor termination with the advantages of flexibility, fast-installation and cost-effective. Currently manufactures can provide various types of mechanical splice connectors of high quality which have low insertion loss and high performance. However, no matter how excellent the mechanical splicing technology is, there are still fiber optic termination failures and bad fiber optic termination due to improper operation. To avoid it, this post is to offer the causes of mechanical splice termination failures.
The Basic of Mechanical splicing
Before finding the cause of mechanical splice failure, the basic of mechanical splicing should be introduced. To finish a mechanical splice, the buffer coatings of fiber optic should be removed mechanically with sharp blades or calibrated stripping tools. In any type of mechanical stripping, the key is to avoid nicking the fiber. Then the fibers will be cleaved. Two fiber ends are then held closely in retaining and aligning a mechanical splice connector with some index matching gel between them. The gel are used to form a continuous optical path between fibers and reduce reflecting losses.
mechanical splicing
Causes of Mechanical Splice Termination Failures
Mechanical splice connector is sensitive to many factors. There are also a large number of factors to cause failures. However, most of the factors are located at the end face of fiber optic. The following is to describe them in details.
Contamination
When facing mechanical splice failures, there would be no argument that contamination is the first thing to think about. There are many ways that contamination can be carried into the fiber termination splices. Generally, there are the following possible causes of splice contamination:
  • Using a dirty cleave tool: as the fiber should be cleave before inserted in the connector, a fiber optic cleaves would be used. If a dirty cleave is used, the contamination would be attached on the end face of the fiber optic and be embedded in the connector. Thus, do remember to clean the surfaces thoroughly with alcohol wipes;
  • Wiping the fiber after cleaving;
  • Setting the connector or fiber down on a dusty surface;
  • Heavy airborne dust environment;
  • Glass fragments from insertion broken fibers, or applying excessive force;
  • Polluted index matching gel.
comtamination
Please note that once the contamination is carried inside the mechanical splice connector, especially with the index matching gel, there would be little possibility to clean them out, which means the connector may be scrapped.
Glass Fragmentation
Improper operation like overexertion when inserting the fiber optic into the mechanical splice connector might break the fiber optic and produce glass fragmentation which will cause air gap and optical failure. Or if a broken fiber if inserted, there will also be optical failure. If the glass fragments are embedded in the connector, they cannot be cleaned out and the connector would be scrapped. Thus, be gentle and carefully when splicing the fiber ends.
glass-fragmentation
Bad Cleave
Cleaving the fiber optic is an important step during fiber optic mechanical splicing. The quality of the cleave can decide the quality of the optical splice transmission to some degree. It is not easy to inspect the cleave quality in the field. There are several possibilities there might cause the bad cleaves:
  • Dull or chipped cleave tool blade
  • The bent tongue on the cleave tool concentrated too much bend stress on the fiber
  • Bending the fiber too much or too tight of a radius
  • Applying no tension or insufficient tension to the fiber while cleaving.
bad cleave
Excessive Fiber Gap
Fiber gap is another factor that might cause the fiber optic termination failure. The fiber optic transmission is very sensitive to the gap between two fiber ends in the mechanical splice connector. Improper operations that might cause the excessive fiber gap are listed as following:
  • Cleaving the fiber without enough lengths;
  • The fiber is not fully inserted, or pulled back during termination;
  • The fiber was not held steady during termination and was pushed back into the fan-out tubing when terminating outdoor cable.
These faults can be corrected one time.
fiber gap
Excessive Cleave Angle
During fiber cleaving, cleave angle can be produced easily and is difficult to be inspected in field. These angles are typically ranging from 1 to 3 degree. Even with precision tool, there might still be cleave angle ranging from 0.5 to 1 degree. The angle is generally produced by bent tongue, fiber bending or insufficient fiber tension.
cleave-angle
However the cleave angles can be corrected by fine tuning with a VFL (visual fault locator). Rotating the fiber while using a VFL and terminate the connector at the position (as shown in the following picture).
VFL-tuning-fiber
Conclusion
Fiber optic mechanical splicing gives quick and high quality result at a low price for fiber optic termination. Choosing the right fiber optic mechanical splice connector and fiber optic cleaver of high quality is not enough. Acknowledge the possible causes to fiber optic termination failures and use the right tools with skills can reduce the risk of termination failure effectively.

Thursday, November 12, 2015

Understand Polarity in MPO System

MPO/MTP technology, which is of high density, flexibility and reliability with scalable, upgradeable properties, is one of the contributors that lead the migration to 40/100GbE. However, the network designers face another challenge which is how to assure the proper polarity of these array connections using multi-fiber MPO/MTP components from end-to-end. Maintain the correct polarity across a fiber network ensures that a transmit signal from any type of active equipment will be directed to receive port of a second piece of active equipment – and vice versa. To ensure the MPO/MTP systems work with correct polarity, the TIA 568 standard provided three methods, which will be introduced in this article.
MPO Connector
To understand the polarity in 40/100 GbE Transmission, the key of MPO technology—MPO connector should be first introduced. MPO connector usually has 12 fibers. 24 fibers, 36 fibers and 72 fibers are also available. Each MTP connector has a key on one of the flat side added by the body. When the key sits on the bottom, this is called key down. When the key sits on top, this is referred to as the key up position. In this orientation, each of the fiber holes in the connector is numbered in sequence from left to right and is referred as fiber position, or P1, P2, etc. A white dot is additionally marked on one side of the connector to denote where the position 1 is. (shown in the following picture) The orientation of this key also determines the MPO cable's polarity.
MPO/MTP connector
Three Cables for Three Polarization Methods
The three methods for proper polarity defined by TIA 568 standard are named as Method A, Method B and Method C. To match these standards, three type of MPO truck cables with different structures named Type A, Type B and Type C are being used for the three different connectivity methods respectively. In this part, the three different cables will be introduced firstly and then the three connectivity methods.
MPO Trunk Cable Type A: Type A cable also known as straight cable, is a straight through cable with a key up MPO connector on one end and a key down MPO connector on the opposite end. This makes the fibers at each end of the cable have the same fiber position. For example, the fiber located at position 1 (P1) of the connector on one side will arrive at P1 at the other connector. The fiber sequence of a 12 fiber MPO Type A cable is showed as the following:
Type A cable
MPO Trunk Cable Type B: Type B cable (reversed cable) uses key up connector on both ends of the cable. This type of array mating results in an inversion, which means the fiber positions are reversed at each end. The fiber at P1 at one end is mated with fiber at P12 at the opposing end. The following picture shows the fiber sequences of a 12 fiber Type B cable.
Type B cable
MPO Trunk Cable Type C: Type C cable (pairs flipped cable) looks like Type A cable with one key up connector and one key down connector on each side. However, in Type C each adjacent pair of fibers at one end are flipped at the other end. For example, the fiber at position 1 on one end is shifted to position 2 at the other end of the cable. The fiber at position 2 at one end is shifted to position 1 at the opposite end etc. The fiber sequence of Type C cable is demonstrated in the following picture.
Type C cable
Three Connectivity Methods
Different polarity methods use different types of MTP trunk cables. However, all the methods should use duplex patch cable to achieve the fiber circuit. The TIA standard also defines two types of duplex fiber patch cables terminated with LC or SC connectors to complete an end-to-end fiber duplex connection: A-to-A type patch cable—a cross version and A-to-B type patch cable—a straight-through version.
duplex patch cable
The following part illustrates how the components in MPO system are used together to maintain the proper polarization connectivity, which are defined by TIA standards.
Method A: the connectivity Method A is shown in the following picture. A type-A trunk cable connects a MPO module on each side of the link. In Method A, two types of patch cords are used to correct the polarity. The patch cable on the left is standard duplex A-to-B type, while on the right a duplex A-to-A type patch cable is employed.Method A
Method B: in Connectivity Method B, a Type B truck cable is used to connect the two modules on each side of the link. As mentioned, the fiber positions of Type B cable are reversed at each end. Therefore standard A-to-B type duplex patch cables are used on both sided.
Method B
Method C: the pair-reversed trunk cable is used in Method C connectivity to connect the MPO modules one each side of the link. Patch cords at both ends are the standard duplex A-to-B type.Method C
Conclusion
Network designer using MPO/MTP components to satisfy the increasing requirement for higher transmission speed, during which one of the big problems—polarity, can be solved by selecting the right types of MPO cables, MPO connectors, MPO cassette and patch cables. The three different polarization methods can be applied according to the satisfy requirements in different situations. For more information about polarity in MPO systems and 40/100GbE transmission polarity solutions, please visit Fiberstore tutorial at "Polarity and MPO Technology in 40/100GbE Transmission".

Sunday, November 8, 2015

Upgrade to High Data Rate Transmission With Parallel Optics

Parallel optics represent a type of optical communication technology as well as the devices on either end of the link that transmit and receive information which are also known as parallel optical transceivers. Compared with traditional optical communication, parallel optical communication employs a different cabling structure for signal transmitting aiming at high-data transmission for short reach multimode fibers that are less than 300 meters. Traditional fiber optic transceivers cannot satisfy the increasing demand for high speed transmission, like 40GbE, while parallel optics technology can be a cost effective solution for 40/100GbE transmission.
Comparison between parallel optics technology and the traditional serial optical communication would better explain what parallel optics is and the reason why it is a cost effective solution to high data rate transmission. The following of this article will offer the comparison between the two optical communication technology from two aspects: connectivity method and key components.
Connectivity Method
Literally, parallel optics and serial optics transmit signals in different ways. In traditional serial optical communication, on each end of the link, there are one transmitter and one receiver. For example, the transmitter on End A communicates to the receiver on End B, sending a single stream of data over a single optical fiber. And a separate fiber is connected between the transmitter on End B and the receiver on End A. In this way, a duplex channel is achieved by two fibers.
2-fiber duplex connection
While in parallel optical communication, duplex transmission is achieved in a different way. A signal is transmitted and received through multiple paths, thus, the parallel optical communication can support higher data rate than the traditional optical communication. This is because, the devices for parallel optic communication on either end of the link contain multiple transmitters and receivers. For instance, in 2010 IEEE 802.3ba approved the 40GBASE-SR4 physical-medium-dependent multimode parallel optical solution, which uses eight fibers to transmit four duplex channels each at 10 Gigabit Ethernet. In this case, four 10Gbps transmitters on End A communicate with four 10Gbps receivers on End B, spreading a single stream of data over four optical fibers at a total data rate of 40Gbps.
Key Components
The parallel optical communication transmitting signals over multiple fibers, which has great advantages over traditional serial optical communication. It also means that it requires different components to support its high data rate transmission.
Connector: As previously mentioned, duplex transmission in serial optical communication uses 2-fiber duplex connectors, like duplex LC connectors to link the optics with other devices, while in parallel optical communication, multi-fibers are used to reach a higher data rate. Thus, multi-fiber connectors, like 12-fiber MPO connectors are used to connect with other devices. MPO connector is one key technology support parallel optical communication. This connectivity method is showed in the following picture?(Tx stands for transmit; Rx stands for receive).
12-fiber MTP parallel connection
Optical transceiver light source: Another complementary technology for parallel transmission is the light source of parallel optics—VCSELs (Vertical Cavity Surface Emission Lasers). Comparing with the edge-emitting semiconductor lasers in the traditional optics, VCSELs have better formed optical output which enables them to couple that energy into optical fibers more efficiently. In addition, VCSELs emit from the top surface, they may be tested while they are part of a large production batch (wafer), before they are cut into individual devices, which dramatically lowers the cost of the lasers. The following chart is about the comparison between VCSELs and edge-emitting semiconductor lasers. Cheaper to manufacture, easier to test, less electrical current required, supporting higher data rate, parallel optics using VCSELs could be a better choice to reach 40/100GbE transmission compared with traditional serial optics.
VCSEL vs Edge-Emitting Laser
Feature VCSEL Edge-Emitting Laser
Power consumption 2-3 mW 20 mW
Beam quality/ease of coupling Better, round low divergence Fine, asymmetric
Speed 10 Gbps 1 Gbps
Temperature stability 0.06 nm/oC 0.25 nm/oC
Specral width 1 nm 1-2 nm
Speckle Low in an array High
 
Parallel Optics for 40/100GbE Transmission
IEEE has already included physical layer specifications and management parameters for 40Gbps and 100Gbps operation over fiber optic cable. Two popular parallel optics solutions for 40Gbps and 100Gbps over multimode fibers are introduced here. For 40G, 40GBASE-SR4 transceiver is usually used, which requires a minimum of eight OM3/OM4 fibers for a transmit and receive link (4 fibers for Tx and 4 fibers for Rx). 100GBASE-SR10 transceiver is for 100Gbps transmission, which requires a minimum of 20 OM3/OM4 fibers for a Tx/Rx link, 10 fibers are used for Tx and the other 10 are for Rx.
40BASE-SR4 and 100BASE-SR10
Conclusion
The capabilities and uses of parallel optics and MPO technology continue to evolve and take shape as higher-speed fiber optic transmission, including 40/100GbE. It is uncertain that parallel optical communication would be the trend in the future. However, many cabling and network experts have pointed out that parallel optical communication supported with MPO technology is currently a way to equip an environment well prepared for the 40/100GbE transmission.

Sunday, November 1, 2015

Migrating to 40/100G With OM3/OM4 Fiber

To meet the continuously increased requirements, data center 40/100G migration is underway. The infrastructure of data centers for the 40G/100G should meet the requirements like high speed, reliability, manageability and flexibility. To meet these requirements, product solutions and the infrastructure topology including cabling must be considered in unison. Cable deployment in the data center plays an important part. The cable used in data center must be selected to provide support for data rate applications not only of today but also the future. Today, two types of multimode fiber—OM3 and OM4 fibers (usually with aqua color)—have gradually become the media choice of data center during 40/100G migration. This article illustrates OM3/OM4 multimode fibers in 40/100G migration in details.
Data Center and Multimode Fibers
Multimode fiber is being widely used in data centers. You might ask why not single-mode fiber? The answer is cost. As is known to all, the price of single-mode fiber is generally more expensive than multimode fiber. In addition multimode fibers provide a significant value proposition when compared to single-mode fiber, as multimode fiber utilizes low cost 850 nm transceivers for serial and parallel transmission. If you had all money you wanted and you’d just run single-mode fiber which has all the bandwidth you need, then you can go plenty of distance. However, this perfect situation would cost a lot of money. Thus, most data center would choose multimode fiber. OM1, OM2, OM3 and OM4 are the most popular multimode fiber. But OM3 and OM4 are gradually taking place of OM1 and OM2 in data centers.
OM
OM stands for optical multimode. OM3 and OM4 are both laser-optimized multimode fibers with 50/125 core, which are designed for use with 850nm VCSELS (vertical-cavity surface-emitting laser) and are developed to accommodate faster networks such as 10, 40 and 100 Gbps. Compared with OM1 (62.5/125 core) and OM2 (50/125 core), OM3 and OM4 can transport data at higher rate and longer distance. The following statistics (850 nm Ethernet Distance) shows the main differences between these four types multimode fibers, which can explain why OM3 and OM4 is more popular in data center now in some extent.
850 nm Ethernet Distance
Fiber Type 1G 10G 40/100G
OM1 300 m 36 m N/A
OM2 500 m 86 m N/A
OM3 1 km 300 m 100 m
OM4 1 km 550 m 150 m
 
Why Use OM3 and OM4 in 40/100G Migration
The Institute of Electrical and Electronics Engineers (IEEE) 802.3ba 40/100G Ethernet Standard was ratified in June 2010. The standard provides specific guidance for 40/100G transmission with multimode and single-mode fibers. OM3 and OM4 are the only multimode fibers included in the standard. The reason why OM3 and OM4 are applied in 40/100G migration is that they can meet the requirements for the migration cabling performance.
Bandwidth, total connector insertion loss and transmission distance are two three main factors should be considered when evaluation the performance needed for cabling infrastructure to meet the requirements for 40/100G. These factors can impact the cabling infrastructure’s ability to meet the standard’s distance of at least 100 meters over OM3 fiber and 150 meters over OM4 fiber. The following explains why OM3/OM4 are the chosen ones for 40/100G migration.
Get Higher Bandwidth With OM3/OM4
Bandwidth is the first reason why OM3 and OM4 are used for 40/100G migration. OM3 and OM4 are optimized for 850nm transmission and have a minimum 2000 MHz?km and 4700 MHz?km effective modal bandwidth (EMB). Comparing the OM1 and OM2 with a maximum 500 MHz?km, advantages of OM3 and OM4 are obvious. With a connectivity solution using OM3 and OM4 fibers that have been measured using the minimum Effective Modal Bandwidth calculate technique, the optical infrastructure deployed in the data center will meet the performance criteria set forth by IEEE for bandwidth.
Get Longer Transmission Distance With OM3/OM4
The transmission distance of fiber optic cables will influence the data center cabling. The manageability and flexibility will be increased with fiber optic cables with longer transmission distance. OM3 fiber and OM4 fiber can support longer transmission distance compare with other traditional multimode fibers. Generally OM3 fibers can run 40/100 Gigabit at 100 meters and OM4 fibers can run 40/100 Gigabit at 150 meters. This high data rate and longer distance cannot be achieved by other traditional multimode fiber like OM1 and OM2. Employing OM3 fiber and OM4 in 40/100G migration is required.
Get Lower Insertion Loss With OM3/OM4
Insertion loss has always been an import factor that technically should consider during the data center cabling. This is because the total connector loss within a system channel impacts the ability to operate over the maximum supportable distance for a given data rate. As total connector loss increased, the supportable distance at that data rate decreases. According to the 40/100G standard, OM3 fiber is specified to a 100m distance with a maximum channel loss of 1.9dB, which includes a 1.5dB total connector loss budget. And OM4 fiber is specified to a 150m distance with a maximum channel loss of 1.5 dB, including a total connector loss budget of 1.0 dB. With low-loss OM3 and OM4 fiber, maximum flexibility can be achieved with the ability to introduce multiple connector mating into the connectivity link and longer supportable transmission distance can be reached.
OM3 or OM4?
Choosing OM3/OM4 is a wise and required choice for data center 40/100G migration. However, OM3 and OM4, which is better? Numerous factors can affect the choice. However, the applications and the total costs are always the main factors to consider to figure out whether OM3 or OM4 is needed.
First, the connectors and the termination of the connectors for OM3 and OM4 fibers are the same. OM3 is fully compatible with OM4. The difference is just in the construction of fiber cable, which makes OM4 cable has better attenuation and can operate higher bandwidth at a longer distance than OM3. Thus, the cost for OM4 fiber is higher than OM3. As 90 percent of all data centers have their runs under 100 meters, choosing OM3 comes down to a costing issue. However, looking in the future, as the demand increases, the cost will come down. Thus, OM4 might be the most viable product at some point soon.
No matter choosing OM3 or OM4, the migration is underway. With good performance like high data rate, long transmission distance and lower inserting loss, OM3/OM4 fiber is a must in data center migration to 40/100G.

Monday, October 19, 2015

G.fast Offers Fiber Speed Ethernet Over Copper

The demand for higher data rates is continuously increasing driven by the applications like Cloud Computing, Big Data and Internet of Things. Meanwhile, the strong market competition makes the network operators to improve the network architecture and deliver high speed services. Pure fiber network should be the best solution. There is no wonder that the fiber network is the trend of the future and it is gradually extended closer to users during the transition from copper-based access networks to pure fiber networks. However, it is not favorable to connect the fiber directly to the customer premises and the cost is high in some cases, like old buildings. To find the fast and cost-effective way to deliver Gigabit speed Ethernet, copper access technology is being applied in some cases. This technology is known as G.fast.
G.fast and FTTdp
G.fast, based on the latest VDSL technology including cross talk cancellation and re-transmission, is designed for use in a 'last-mile' of less than 250 meters. Combining the advantages of fiber optic access technology and copper access technology, G.fast can deliver data at fiber speed to the customers using telephone copper wires.
The problem with G.Fast is that its ultra-fast speeds only work over very short distances. To shorten the copper distance, FTTdp is usually applied with G.fast. "dp" here stands for "distribution point". This solution brings the fiber optic cable out of street cabinets and moves it closer to home via the distribution point. The following network diagram shows the difference of FTTH and FTTdp using G.fast. The blue lines represent fiber optic cable, the red ones represent copper wire.
G.fast and HTTdp
G.fast Shifts the Limits of Copper
It seems that there is no need for copper access in building a FTTx connection. But in practice, connecting the fiber directly to the customer premises causes some disadvantages which can be solved by G.fast.
There might be many difficulties when deploying fibers to the user homes, especially some existing buildings. Sometime it is even not possible to deploy fibers to the user homes. In addition, most in-house telephone installations still rely on copper cables for most existing and newly constructed buildings because fibers are expensive and difficult to handle. There is no need to deploy fiber optic cable in building and home when delivering Gigabit Ethernet with G.fast.
The fiber optic based customers premises equipment (CPE) are usually installed by technician. Compared with fiber optic connections, copper-based CPE installation is simple. Just connecting the CPE to the telephone plug with the delivered cable would finish the installation, which can be installed by customer. Thus, G.fast can save the cost for new users and makes the home installation much easier.
Optical fibers can be broken or have transmission loses when wrapped around curves and optical fibers require more protection around the cable compared to copper. What’s more, the fault location from the CPE is not easy. It would cost more to maintain the fiber connections compared with copper connections achieved by G.fast.
G.fast Paves the Way to FTTH
At first glance, G.fast is limiting the transmission from copper to fiber. Actually, G.fast accelerates the deployment of fiber optic networks. It cost a lot of time and money to process the paperwork and get permission of the subscriber before deploying the fiber optic cable. The processing is complicated. Hardware foundation is the main advantages of G.fast which eliminates the need to rewire the whole building and still allows a noteworthy uplift in access speeds. Copper is everywhere in telecommunication network. The hybrid copper/fiber approach—G.fast making full use of the telephone wires in the buildings actually makes the customers closer to optical fibers in time save and cost save manners. In this way, the transmission from copper to fiber is actually being promoted by G.fast.
Weighing time, broadband speed and cost, operators figure out that applying G.fast in FTTH is an economical and time-saving way to bring Gigabit speed Ethernet to the users. To capture market share of broadband service, some network operators are considering to use G.fast. Alcatel-Lucent and communications services company BT have already started a consumer trial of G.fast technology in Gosforth (situated in North-Eastern England), for offering ultra-broadband access to consumers.

Sunday, October 18, 2015

Do You Know Digital Diagnostic Monitoring?

Cisco announced the end of sale of its SFP transceiver Cisco GLC-SX-MM transceiver and published a replacement—Cisco GLC-SX-MMD transceiver in 2012. The module numbers of the two transceiver only differ in one letter "D". This "D" mainly represents a function of Cisco GLC-SX-MMD transceiver and is inherited by most of optical transceivers offered today. It is the main reason why Cisco GLC-SX-MMD transceiver can replace its predecessor. What is this "D"? Why the GLC-SX-MMD can replace GLC-SX-MM? This article is to offer the answers to these questions.
What Is Digital Diagnostic Monitoring (DDM)?
"D" in GLC-SX-MMD represents the DDM function which is short for digital diagnostic monitoring according to the industry standard MSA (Multi-Source Agreement) SFF-8472 and is also known as DOM (Digital Optical Monitoring). When buy fiber optic transceiver today, you will have the option with or without DDM/DOM. And most of the modern transceivers are with the DDM function. This technology allows the user to monitor real-time parameters of the fiber optic transceivers, like optical input/output power, temperature, laser bias current, and transceiver supply voltage, etc.
What Can Digital Diagnostic Monitoring Do?
Literally, DDM function can provide component monitoring on transceiver applications in details. However, DDM’s application is not limited to this. The SFF-8472 added DDM interface and outlined that DDM interface is an extension of the serial ID interface defined in GBIC specification, as well as the SFP MSA. DDM interface includes a system of alarm and warning flags which alert the host system when particular operating parameters are outside of a factory set normal operating. Thus, DDM interface can also enable the end user with the capabilities of fault isolation and failure prediction. This part is to illustrate what can be done with DDM.
Component Monitoring: The DDM enables the end user to monitor key parameters in the performance of the fiber optic transceiver including the following:
  • Transceiver temperature
  • Transceiver supply voltage
  • Laser bias current
  • Transmit average optical power
  • Received optical modulation amplitude (OMA) or Average Optical Power
The real-time diagnostic parameters can be monitored to alert the system when the transceiver’s specified operating limits are exceeded and compliance cannot be ensured.The following picture shows the eye diagram illustrating optical figures of merit.
DDM eye diagram
Fault isolation: The DDM function can be used to isolate the particular location of fault in fiber optic network system. Combining the DDM interface status flags, transceiver hard pins and diagnostic parametric monitor data, the specific location and cause of a link failure can be pinpointed.
Failure prediction: The DDM can also be used to help in failure prediction on fiber optic links, which is based on the transceiver parametric performance. Although, this application is not yet fully mature, but there is still room for improvement. There are two basic types of failure conditions that can be seen on fiber optic transceivers:
  • Device faults—A device non-operation or malfunction. Typically applied more to transmitter performance, due to nature of semiconductor lasers.
  • High error rate conditions—Operating conditions are such that transceiver is operating at its signal-to-noise limit. Applies more to fiber optic receiver performance.
Providing parameter monitoring, fault isolation, and failure prediction, fiber optic transceivers with DDM help to ensure that the business can be proactive in preventative maintenance of the network and ensure business continuity. And it would easy to explain why modern transceivers are with DDM and why GLC-SX-MMD can replace GLC-SX-MM. It is irresistible development trend of industry and technology.
What should be mentioned is that although optical transceivers with DDM are much popular than those without DDM, some user still use the older optical transceivers in consideration of the upgrading costs. To satisfy the customers’ needs, optical transceivers with DDM and without DDM are provided by the vendors like Fiberstore.